Lets explain what the Louvre classifications mean. BS EN 13030:2001 sets out the guidelines for the testing and classification of all weather or performance louvres. During testing, the resistance to airflow is assessed and the louvres are subjected to 75mm/hr. of water, blown against a 1m x 1m louvre at a velocity of 13m/s. The louvre is then given a 3 part classification:
Part 1: Louvre Effectiveness (or Penetration Class) rated A – D
This classification, rated A – D designates the “effectiveness” Class of the weather louvre against water (rain) penetration. Each class covers a specific range and it can be seen from the table below that a Class A is significantly more effective than the Class B below it:
Class | Effectiveness (PC) | Maximum allowable penetration of rain l/h.m² |
---|---|---|
A | 1 to 0.99 | 0.75 |
B | 0.989 to 0.95 | 3.75 |
C | 0.949 to 0.80 | 15 |
D | Below 0.8 | Greater than 15 |
Part 2: Airflow Class rated 1 – 4:
This classification, rated 1 – 4 designates the louvres ability to allow air to pass through it and is determined by establishing the Discharge Loss Coefficient (DLC) at various airflow velocities. Each class covers a specific range, as can be seen in the table below. The higher the DLC the less resistant to air the louvre is. In simple terms, a hole in the wall with no louvre would have a discharge loss coefficient of 1. The Airflow Class gives a guide to the M&E consultants of how the louvre performs at various ventilation rates and the actual DLC figure is used to establish the actual area of louvre required.
Airflow Class | Discharge Loss Coefficient (DLC) | Rating |
---|---|---|
1 | 0.4 and Above | Excellent |
2 | 0.3 to 0.399 | Very Good |
3 | 0.2 to 0.299 | Good |
4 | 0.199 and below | Fair |
Part 3: Overall Performance:
This is calculated by multiplying the effectiveness by the coefficient, giving you an “Overall Performance” rating. It should be noted that this should not be used as the sole determining factor when choosing louvres as it can mask poor weather performance on a louvre with good airflow.
Conclusion
So, that’s the science bit over with! What can be seen is that there are varying degrees of weather protection afforded by louvres and even within the top classification, Class A, there is a range of 1% variation allowed.
To gain a Class A classification a louvre must allow no more than 0.75 litres of water through it. Without the full test data there is nothing to distinguish a louvre that allows 0 litres of water through it and a louvre that allows the maximum-therefore not all Class A Louvres can be considered equal in terms of rain penetration.
Rain penetration isn’t the only factor in choosing a weather louvre however. A solid wall will allow 0 litres of water through it, but it will also allow no airflow! When specifying louvre a balance between airflow and water ingress is needed, so it is vital to first consider the needs of the building (or the room the louvres are being fitted to).
Construction Specialties has over 50 years of experience in designing, manufacturing and installing Performance Louvre, in projects large and small, and will be happy to assist you in choosing the right louvre for your project.
What next?
- Download the CS Louvre Specification Guide
- Read: How to Correctly Specify Building & Architectural Louvres
- Read: Building & Architectural Louvres Explained
- Read: How to Calculate Louvre Pressure Drop
- Get in touch with the experts to discuss your requirements on 01296 652800 or email sales@c-sgroup.co.uk