Construction Specialties Storm Resistant Louvres repel up to 100% of wind-driven rain. Available in both horizontal and vertical configurations.
Ideal when you:
- Need 100% resistance to wind-driven rain
- Expect winds as high as 50 mph that drive around 20mm of water per hour
- Must integrate the louvre into the building’s total design or house them behind architectural grilles, detailing or continuous-line louvres
- Can’t use a plenum due to cost or space considerations
- Plan to house sensitive equipment adjacent to the louvre system
- Need a louvre to integrate with a CENTRIA Formawall® Dimension Series® panel system
Storm Resistant Models
All louvres listed below are tested in accordance with AS/NZS 4740:2000 (R2016). Tests are conducted using full size aerodynamic test equipment.
RS-4300
Volume Flow rate (m³/s) | 0 | 0.5 | 1 | 1.5 | 2 | 2.5 | 3 | 3.5 | |
---|---|---|---|---|---|---|---|---|---|
RS-4300 | Performance Level | A | A | B | B | C | C | D | D |
Effectiveness (%) | 100 | 99 | 98 | 96 | 91 | 91 | 77 | 60 |
RS-5300
Volume Flow rate (m³/s) | 0 | 0.5 | 1 | 1.5 | 2 | 2.5 | 3 | 3.5 | |
---|---|---|---|---|---|---|---|---|---|
RS-5300 | Performance Level | A | A | A | A | B | B | C | D |
Effectiveness (%) | 100 | 100 | 100 | 99.1 | 98.3 | 96.8 | 92.6 | 78.7 |
RSH-5700
** Tested with higher wind speed and rainfall intensity than the requirements from the AS/NZS 4740:2000 (R2016).
Volume Flow rate (m³/s) | 0 | 0.5 | 1 | 1.5 | 2 | 2.5 | 3 | 3.5 | 4 | 4.5 | 5 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
RSH-5700 | Performance Level | A | A | A | A | A | A | A | A | A | B | C |
Effectiveness (%) | 100 | 100 | 100 | 100 | 100 | 100 | 99.9 | 99.5 | 99.4 | 98.1 | 94.9 |
RSV-5700
** Tested with higher wind speed and rainfall intensity than the requirements from the AS/NZS 4740:2000 (R2016).
Volume Flow rate (m³/s) | 0 | 0.5 | 1 | 1.5 | 2 | 2.5 | 3 | 3.5 | 4 | 4.5 | 5 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
RSV-5700 | Performance Level | A | A | A | A | A | A | A | A | A | A | A |
Effectiveness (%) | - | - | - | - | - | - | - | - | - | 100 | 99.8 |
RS-5605
** Tested with higher wind speed and rainfall intensity than the requirements from the AS/NZS 4740:2000 (R2016).
Volume Flow rate (m³/s) | 0 | 0.5 | 1 | 1.5 | 2 | 2.5 | 3 | 3.5 | 4 | 4.5 | 5 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
RS5605 | Performance Level | A | A | A | A | A | A | A | A | A | A | A |
Effectiveness (%) | - | - | - | - | - | - | - | - | 99.4 | 99.3 | 99.2 |